Worked example · Facility sizing

Bakery freezer with a short loading window

A bakery loads warm dough into the freezer after a production run and needs it cooled during a fixed four-hour window.

Sized capacity
14.57kW
Refrig. tons
4.14TR
24-hour load
5.08kW
Product load
1.9kW
Edit inputs

Inputs

Edit any value to recalculate.

Room envelope

Use assembly R-values. The floor can have a different boundary temperature.

m
m
m
°C
°C
°C
m²·K/W
m²·K/W
m²·K/W
Door air exchange

One exchange replaces one room volume. Enter effective daily exchanges after door controls.

changes/day
%
%
Product cooling
kg/day
°C
°C
kJ/(kg·K)
kJ/(kg·K)
kJ/kg
h
Internal loads & runtime

This sizing screen uses 16–20 available compressor hours per day.

kW
h/day
kW
h/day
kW
h/day
kW
h/day
%
h/day

The product pull-down window controls the equipment capacity estimate.

Heat entering the walk-in

Heat entering the walk-inThe stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.Surrounding air29 °CRoom setpoint-20 °CVolume 67.2 m³Positive gains / 24-hour averagePanelsDoor airProductInternal

The stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.

Calculation breakdown

Four walls
0.61kW
Ceiling
0.23kW
Floor
0.17kW
Net panel transmission
1.01kW
Door infiltration incl. moisture
1.56kW
Product heat per day
163,966kJ
Lighting heat
0.08kW
Fan heat
0.37kW
Occupant heat
0.08kW
Retained defrost heat
0.08kW
Runtime-adjusted capacity
6.09kW
Product-window capacity
14.57kW
Inside box volume
67.2m³

Work through this case

  1. Product heat per day 163,966kJ
  2. Product-window capacity 14.57kW
  3. Sized capacity 14.57kW

Compare capacity for the four-hour batch with the runtime-adjusted daily load. Warming or rearranging the delivery profile changes the comparison.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Panel transmission

Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]

Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.

Door infiltration

Q = V × exchanges/day × ρda × Δh / 86,400

The air-change method uses the entering dry-air density and moist-air enthalpy difference at standard atmospheric pressure. In a freezer it adds freezing heat for moisture removed from the incoming air. This is a daily screening estimate.

Product cooling and internal loads

E = m × (c₊ΔT₊ + Lf + c₋ΔT₋)

The fusion term applies to product crossing below its freezing point. Lighting, fans, occupancy and retained defrost heat are averaged over 24 hours. Respiration heat for living produce can be estimated with the produce tool and carried as an additional load in a detailed design.

Compressor sizing

Qsize = max(Qavg × 24 / runtime, Qbase + E / cooling window)

Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.

References

Questions and answers

What should I check in the bakery freezer with a short loading window example?

Compare capacity for the four-hour batch with the runtime-adjusted daily load. Warming or rearranging the delivery profile changes the comparison.