Panel transmission
Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]
Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.
Facility sizing
Size a six-sided commercial cold room from insulation, door air exchanges, product pull-down, internal heat and compressor runtime.
Edit any value to recalculate.
The stacked bar shows positive average gains. The sizing capacity also accounts for runtime and the product cooling window.
Open a case with its assumptions loaded, then edit the inputs.
A small foodservice cooler receives a daily load of chilled ingredients, with a separate temperature boundary below the floor.
A supermarket back-room freezer receives a mix of unfrozen replenishment product and electric defrost heat.
A holding room receives already-frozen seafood and cools it several more degrees before long-term storage.
A freezer opens frequently onto a warm, humid dock while the air in the box stays below freezing.
A deli cooler has room-temperature walls and ceiling but sits over a colder conditioned space.
A bakery loads warm dough into the freezer after a production run and needs it cooled during a fixed four-hour window.
A flower cooler receives product close to the room setpoint and carries almost no daily product heat.
Q = Σ[A × (Tₒᵤₜ − Tᵣₒₒₘ) / R]
Area covers four walls, a ceiling, and a floor. Each assembly U-value is 1/R. A colder adjacent boundary can contribute a cooling credit.
Q = V × exchanges/day × ρda × Δh / 86,400
The air-change method uses the entering dry-air density and moist-air enthalpy difference at standard atmospheric pressure. In a freezer it adds freezing heat for moisture removed from the incoming air. This is a daily screening estimate.
E = m × (c₊ΔT₊ + Lf + c₋ΔT₋)
The fusion term applies to product crossing below its freezing point. Lighting, fans, occupancy and retained defrost heat are averaged over 24 hours. Respiration heat for living produce can be estimated with the produce tool and carried as an additional load in a detailed design.
Qsize = max(Qavg × 24 / runtime, Qbase + E / cooling window)
Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.
Use door-use observations or an engineering estimate for the volume of air exchanged over a day. Door opening duration, dock temperature, pressure imbalance, and strip curtains can change this input substantially.
A batch arriving over a short period adds its whole thermal load within that window. Sizing only from the daily average can leave too little capacity during receiving.
ColdChainLab · Engineering calculation
Metric SI · https://calcsheetlab.com/coldchainlab/walk-in-cooler-freezer-load/
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.