ControlLoopLab
Home PID tuningWorked example

Conveyor dryer with transport delay

A downstream moisture sensor sees the result of heater changes only after product leaves the drying zone.

Model inputs

Process model
s
s
Controller
s

Process reaction & setpoint response

Dead-time dominant
Kc
0.32653
Ti
16s
Td
0s
Overshoot
3.2504%
Open- and closed-loop FOPDT responseClosed-loop responseoutput098.5197296394−0.08260.3170.7161.12Time (s)Open-loop reactionoutput098.5197296394−0.0560.2150.4850.756Time (s)SetpointClosed-loop outputOpen-loop output
G(s) = Kp exp(−θs) / (1 + τp s)

Calculated results

ISA Kc
0.32653
ISA Ti
16s
ISA Td
0s
Parallel Kp
0.32653
Parallel Ki
0.0204081/s
Parallel Kd
0s
Dead-time ratio θ/τ
2.125
Overshoot
3.2504%
2% settling time
204.89s
Peak |control effort|
1.4863
Setpoint IAE
74.695s
Steady state (model)
1
Simulation step
0.20341s
Simulated window
394s
  • Dead-time dominant model. Feedback cannot react during the transport delay.

Model and interpretation

Full methodology

Fit the process first

Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.

Match the controller form

SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.

Read the simulation window

The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.