ControlLoopLab
Home PID tuningWorked example

Proportional-only damper position

A damper position loop is intentionally run without integral action during a response comparison.

Model inputs

Process model
s
s
Controller
s

Process reaction & setpoint response

Settled in model
Kc
1.5814
Ti
Off
Td
0s
Overshoot
0%
Open- and closed-loop FOPDT responseClosed-loop responseoutput08.6117.225.834.5−0.080.3070.6931.08Time (s)Open-loop reactionoutput08.6117.225.834.5−0.080.3070.6931.08Time (s)SetpointClosed-loop outputOpen-loop output
G(s) = Kp exp(−θs) / (1 + τp s)

Calculated results

ISA Kc
1.5814
ISA Ti
Off
ISA Td
0s
Parallel Kp
1.5814
Parallel Ki
01/s
Parallel Kd
0s
Dead-time ratio θ/τ
0.13235
Overshoot
0%
2% settling time
4.2845s
Peak |control effort|
1.5814
Setpoint IAE
14.255s
Steady state (model)
0.61261
Simulation step
0.020579s
Simulated window
34.45s
  • P-only uses the proportional gain of the selected PI rule and leaves a steady-state offset.

Model and interpretation

Full methodology

Fit the process first

Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.

Match the controller form

SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.

Read the simulation window

The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.