Heat exchanger outlet Lambda tuning

A heat exchanger outlet temperature loop uses an identified self-regulating gain after a small valve step.

Model inputs

Process model
s
s
Controller
s

Process reaction & setpoint response

Settled in model
Kc
1.1458
Ti
44s
Td
0s
Overshoot
0%
Open- and closed-loop FOPDT responseClosed-loop responseoutput0112223335446−0.080.3070.6931.08Time (s)Open-loop reactionoutput0112223335446−0.1280.4911.111.73Time (s)SetpointClosed-loop outputOpen-loop output
G(s) = Kp exp(−θs) / (1 + τp s)

Calculated results

ISA Kc
1.1458
ISA Ti
44s
ISA Td
0s
Parallel Kp
1.1458
Parallel Ki
0.0260421/s
Parallel Kd
0s
Dead-time ratio θ/τ
0.13636
Overshoot
0%
2% settling time
73.215s
Peak |control effort|
1.3007
Setpoint IAE
24s
Steady state (model)
1
Simulation step
0.24252s
Simulated window
446s

Model and interpretation

Full methodology

Fit the process first

Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.

Match the controller form

SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.

Read the simulation window

The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.