Pump station Ziegler–Nichols reaction curve
A discharge-pressure transmitter records a small speed step while a pressure controller is in manual.
Model inputs
- Process gain Kp
- 1.2
- Time constant τp
- 12 s
- Dead time θ
- 3 s
- Tuning rule
- Ziegler–Nichols open-loop
- Controller action
- PID
- Controller form
- ISA ideal
Model inputs
Process reaction & setpoint response
Settled in model- Kc
- 4
- Ti
- 6s
- Td
- 1.5s
- Overshoot
- 58.763%
Calculated results
- ISA Kc
- 4
- ISA Ti
- 6s
- ISA Td
- 1.5s
- Parallel Kp
- 4
- Parallel Ki
- 0.666671/s
- Parallel Kd
- 6s
- Dead-time ratio θ/τ
- 0.25
- Overshoot
- 58.763%
- 2% settling time
- 29.201s
- Peak |control effort|
- 5.982
- Setpoint IAE
- 7.6847s
- Steady state (model)
- 1
- Simulation step
- 0.032316s
- Simulated window
- 72s
- Reaction-curve rules are aggressive starting points. Compare effort and overshoot before commissioning.
Model and interpretation
Full methodologyFit the process first
Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.
Match the controller form
SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.
Read the simulation window
The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.