FOPDT process PID tuning
Tune a first-order plus dead-time process and compare its open-loop reaction curve with a simulated closed-loop setpoint step.
Model inputs
- Process gain Kp
- 2
- Time constant τp
- 30 s
- Dead time θ
- 8 s
- Tuning rule
- Skogestad SIMC
- Controller action
- PI
- Controller form
- ISA ideal
- Closed-loop time constant τc
- 12 s
Model inputs
Process reaction & setpoint response
Settled in model- Kc
- 0.75
- Ti
- 30s
- Td
- 0s
- Overshoot
- 0.043634%
Calculated results
- ISA Kc
- 0.75
- ISA Ti
- 30s
- ISA Td
- 0s
- Parallel Kp
- 0.75
- Parallel Ki
- 0.0251/s
- Parallel Kd
- 0s
- Dead-time ratio θ/τ
- 0.26667
- Overshoot
- 0.043634%
- 2% settling time
- 43.315s
- Peak |control effort|
- 0.94923
- Setpoint IAE
- 20.01s
- Steady state (model)
- 1
- Simulation step
- 0.18746s
- Simulated window
- 308s
Model and interpretation
Full methodologyFit the process first
Subtract the pre-step baseline. Divide the eventual output change by the input step for Kp. Estimate the delay and the time to 63.2% of the final change after the delay. Negative process gain gives negative controller gains under the stated feedback convention.
Match the controller form
SIMC PI uses Kc = τp/[Kp(τc+θ)] and Ti = min(τp, 4(τc+θ)). Extended SIMC PID adds θ/3 in the series form. Lambda PI keeps Ti = τp. The Lambda PID setting uses the first-order Padé IMC rule. Ziegler–Nichols and Cohen–Coon use open-loop reaction-curve coefficients.
Read the simulation window
The setpoint changes by one output unit. A zero-order-held plant update splits the discrete step at the fractional dead time. The controller integrates error and uses a filtered derivative on measurement (Td/10). Overshoot and 2% settling reference the predicted steady state. IAE integrates setpoint error over the finite run. Actuator limits, noise and windup are outside this model.