RTD & NTC linearization
Convert Pt100, Pt1000 or NTC sensor resistance to temperature and estimate RTD wiring error or thermistor divider sensitivity.
Model inputs
- Sensor model
- IEC 60751 Pt100
- Known quantity
- Temperature → resistance
- Sensor temperature
- 80 °C
- One-way lead run
- 30 m
- Copper conductor
- 0.326 mm²
- Lead temperature
- 25 °C
- 3-wire lead mismatch
- 2 %
- Excitation current
- 1 mA
- Self-heating factor
- 0.4 °C/mW
Model inputs
Fractional AWG shows the equivalent copper area.
Calibration curves & sensor wiring
IEC nominal curve- Temperature
- 80°C
- Resistance
- 130.9Ω
- 2-wire error
- 8.49°C
- Self-heating
- 0.052359°C
Calculated results
- Nominal temperature
- 80°C
- Sensing resistance
- 130.9Ω
- Local sensitivity
- 0.38159Ω/°C
- Single lead resistance
- 1.6178Ω
- 2-wire apparent resistance
- 134.13Ω
- 2-wire lead error
- 8.49°C
- 3-wire apparent resistance
- 130.93Ω
- 3-wire mismatch error
- 0.084792°C
- Sensor dissipation
- 0.1309mW
- Self-heating error
- 0.052359°C
Model and interpretation
Full methodologyUse the nominal platinum curve
A = 3.9083×10⁻³, B = −5.775×10⁻⁷ and C = −4.183×10⁻¹². The nominal range is −200 to 850 °C. Actual probe tolerance, calibration coefficients and certified operating span come from its datasheet.
Budget wiring and self-heating separately
A 2-wire readout includes twice the lead resistance. For 3-wire compensation the residual is modeled as one lead resistance times the signed mismatch percentage. Self-heating is I²R times the supplied temperature rise per mW.
Use the correct sensor family
NTC conversion uses Beta or 1/TK = A + B ln R + C(ln R)³. The divider node sits between a pull-up and the grounded NTC. Thermocouple cold-junction compensation uses a different model and is outside this tool.