CRAC / CRAH airflow & rack ΔT calculator

Calculate supply CFM or rack temperature rise using sensible load, elevation, coil SHR and hot/cold aisle air losses.

Engineering schematic

Sensible air path

Live
Sensible air path SUPPLY FLOW 2.42 m³/s. RACK ΔT 12 K. SENSIBLE 30 kW. DENSITY 1.2 kg/m³. See the results table for the full readout. SUPPLY FLOW2.42m³/sRACK ΔT12KSENSIBLE30kWDENSITY1.2kg/m³ CRAC/CRAH95% SHRHot returnCold aisle2.07 m³/s12 Krack rise14.5% delivery lossSensible load / rated sensible capacity0%75% usedLimit 100%

Sensible capacity headroom 9.9 kW

Inputs

Rack and cooling unit
kW
kW
kWₜₕ
%
Air path

Bypass and recirculation reduce the fraction of supply air that delivers effective rack cooling.

K
m
%
%

Calculation details

MeasureValue
Rack and room sensible load30 kW
Air density at site elevation1.2 kg/m³
Effective delivery fraction85.5 %
Rack air temperature rise12 K
Useful rack airflow2.071 m³/s
Required or measured supply airflow2.422 m³/s
Airflow delivery penalty0.351 m³/s
Total coil duty at entered SHR31.58 kWₜₕ
Rated sensible coil capacity39.9 kWₜₕ
Rated latent coil capacity2.1 kWₜₕ
Sensible capacity headroom9.9 kW

Calculation method

  • Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
  • CFM ≈ 3.16 × W ÷ ΔT°F at reference density
  • Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]

Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.

Engineering limits

The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.

Worked examples