Low SHR leaves a sensible shortfall

A 48 kW total-capacity coil at 73% SHR serves a 41 kW sensible load. Assess nameplate headroom.

Engineering schematic

Sensible air path

Live
Sensible air path SUPPLY FLOW 2.9 m³/s. RACK ΔT 14 K. SENSIBLE 41 kW. DENSITY 1.2 kg/m³. See the results table for the full readout. SUPPLY FLOW2.9m³/sRACK ΔT14KSENSIBLE41kWDENSITY1.2kg/m³ CRAC/CRAH73% SHRHot returnCold aisle2.43 m³/s14 Krack rise16.3% delivery lossSensible load / rated sensible capacity0%117% usedLimit 100%

Sensible capacity headroom -6 kW

Inputs

Rack and cooling unit
kW
kW
kWₜₕ
%
Air path

Bypass and recirculation reduce the fraction of supply air that delivers effective rack cooling.

K
m
%
%

Calculation details

MeasureValue
Rack and room sensible load41 kW
Air density at site elevation1.2 kg/m³
Effective delivery fraction83.72 %
Rack air temperature rise14 K
Useful rack airflow2.426 m³/s
Required or measured supply airflow2.898 m³/s
Airflow delivery penalty0.472 m³/s
Total coil duty at entered SHR56.16 kWₜₕ
Rated sensible coil capacity35.04 kWₜₕ
Rated latent coil capacity12.96 kWₜₕ
Sensible capacity headroom-5.96 kW

Starting calculation

  1. Add IT and room heat for 41 kW sensible. The bypass and recirculation assumptions give 83.72% effective delivery.
  2. At 14 K and 1.2 kg/m³, the required fan supply is 2.898 m³/s (6,140 CFM).

Read the sensible capacity row before sizing airflow. The total nameplate includes latent cooling.

Calculation method

  • Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
  • CFM ≈ 3.16 × W ÷ ΔT°F at reference density
  • Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]

Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.

Engineering limits

The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.