High-elevation CRAH airflow
A 42 kW group at 1,650 m needs additional supply volume because the local air density is lower.
Engineering schematic
Sensible air path
Sensible capacity headroom 11.4 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Rack and room sensible load | 45 kW |
| Air density at site elevation | 0.9831 kg/m³ |
| Effective delivery fraction | 89.28 % |
| Rack air temperature rise | 11 K |
| Useful rack airflow | 4.136 m³/s |
| Required or measured supply airflow | 4.633 m³/s |
| Airflow delivery penalty | 0.497 m³/s |
| Total coil duty at entered SHR | 47.87 kWₜₕ |
| Rated sensible coil capacity | 56.4 kWₜₕ |
| Rated latent coil capacity | 3.6 kWₜₕ |
| Sensible capacity headroom | 11.4 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Add IT and room heat for 45 kW sensible. The bypass and recirculation assumptions give 89.28% effective delivery.
- At 11 K and 0.983 kg/m³, the required fan supply is 4.633 m³/s (9,817 CFM).
Set the elevation to zero to isolate density from the other air-path effects.
Calculation method
- Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
- CFM ≈ 3.16 × W ÷ ΔT°F at reference density
- Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]
Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.
Engineering limits
The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.
Related worked examples
DataCenterPUELab · Calculation sheet
High-elevation CRAH airflow
Sensible capacity headroom 11.4 kW
Inputs
- IT heat load
- 42 kW
- Other sensible heat
- 3 kW
- Total coil capacity
- 60 kWₜₕ
- Sensible heat ratio
- 94 %
- Calculate
- Supply airflow
- Target rack ΔT
- 11 K
- Site elevation
- 1650 m
- Supply air bypass
- 7 %
- Hot air recirculation
- 4 %
Results
- Rack and room sensible load
- 45 kW
- Air density at site elevation
- 0.9831 kg/m³
- Effective delivery fraction
- 89.28 %
- Rack air temperature rise
- 11 K
- Useful rack airflow
- 4.136 m³/s
- Required or measured supply airflow
- 4.633 m³/s
- Airflow delivery penalty
- 0.497 m³/s
- Total coil duty at entered SHR
- 47.87 kWₜₕ
- Rated sensible coil capacity
- 56.4 kWₜₕ
- Rated latent coil capacity
- 3.6 kWₜₕ
- Sensible capacity headroom
- 11.4 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.