Airside with humidity lockout hours
The six bins represent only 6,000 screened hours. The remaining annual hours require mechanical cooling.
Engineering schematic
Annual climate-bin dispatch
4,225 h of equivalent full-free cooling per year.
Inputs
Calculation details
| Measure | Value |
|---|---|
| Full-free outdoor cutoff | 19 °C |
| Mechanical cooling threshold | 25 °C |
| Full-free cooling hours | 3,600 h |
| Partial cooling hours | 1,250 h |
| Mechanical cooling hours | 3,910 h |
| Unentered hours assigned to mechanical | 2,760 h |
| Equivalent full-free cooling hours | 4,225 h |
| All-mechanical baseline energy | 2,847 MWh |
| Energy in full-free bins | 216 MWh |
| Energy in partial bins | 240.62 MWh |
| Energy in mechanical bins | 1,270.75 MWh |
| Modeled annual cooling energy | 1,727.38 MWh |
| Annual cooling energy savings | 1,119.63 MWh |
| Baseline cooling energy saved | 39.33 % |
| Annual energy cost savings | 134,355 $ |
| Annual grid emissions avoided | 391.87 t CO₂e |
Update the highlighted inputs to see the results.
Starting calculation
- Subtract 4 K of approach to get a 19 °C full-free cutoff. The entered bins give 3,600 full-free and 1,250 partial hours.
- Weight plant power by each bin. Annual cooling energy moves from 2,847 MWh to 1,727.38 MWh.
The unentered hours stay mechanical even when the entered air temperatures would otherwise allow economization.
Calculation method
- Full-free cutoff = applicable setpoint − total approach
- Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
- Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000
Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.
Engineering limits
ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.
Related worked examples
DataCenterPUELab · Calculation sheet
Airside with humidity lockout hours
4,225 h of equivalent full-free cooling per year.
Inputs
- Economizer type
- Airside · dry-bulb
- Inlet class
- ASHRAE A1
- IT inlet air setpoint
- 23 °C
- Total approach
- 4 K
- Partial cooling band
- 6 K
- Plant cooling load
- 1758.426421 kWₜₕ
- Mechanical plant input
- 0.1848243384646 kW/kWₜₕ
- Economizer plant input
- 0.03412141633193 kW/kWₜₕ
- Energy tariff
- 0.12 $/kWh
- Grid emissions factor
- 350 g/kWh
- Bin 1 temperature
- -8 °C
- Bin 1 hours
- 450 h
- Bin 2 temperature
- 3 °C
- Bin 2 hours
- 650 h
- Bin 3 temperature
- 10 °C
- Bin 3 hours
- 1000 h
- Bin 4 temperature
- 17 °C
- Bin 4 hours
- 1500 h
- Bin 5 temperature
- 22 °C
- Bin 5 hours
- 1250 h
- Bin 6 temperature
- 29 °C
- Bin 6 hours
- 1150 h
Results
- Full-free outdoor cutoff
- 19 °C
- Mechanical cooling threshold
- 25 °C
- Full-free cooling hours
- 3,600 h
- Partial cooling hours
- 1,250 h
- Mechanical cooling hours
- 3,910 h
- Unentered hours assigned to mechanical
- 2,760 h
- Equivalent full-free cooling hours
- 4,225 h
- All-mechanical baseline energy
- 2,847 MWh
- Energy in full-free bins
- 216 MWh
- Energy in partial bins
- 240.62 MWh
- Energy in mechanical bins
- 1,270.75 MWh
- Modeled annual cooling energy
- 1,727.38 MWh
- Annual cooling energy savings
- 1,119.63 MWh
- Baseline cooling energy saved
- 39.33 %
- Annual energy cost savings
- 134,355 $
- Annual grid emissions avoided
- 391.87 t CO₂e
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.