Waterside plant without partial operation
The operating sequence is full-free or mechanical. The plant always switches over at one outdoor threshold.
Engineering schematic
Annual climate-bin dispatch
3,500 h of equivalent full-free cooling per year.
Inputs
Calculation details
| Measure | Value |
|---|---|
| Full-free outdoor cutoff | 12 °C |
| Mechanical cooling threshold | 12 °C |
| Full-free cooling hours | 3,500 h |
| Partial cooling hours | 0 h |
| Mechanical cooling hours | 5,260 h |
| Unentered hours assigned to mechanical | 0 h |
| Equivalent full-free cooling hours | 3,500 h |
| All-mechanical baseline energy | 4,169.76 MWh |
| Energy in full-free bins | 367.5 MWh |
| Energy in partial bins | 0 MWh |
| Energy in mechanical bins | 2,503.76 MWh |
| Modeled annual cooling energy | 2,871.26 MWh |
| Annual cooling energy savings | 1,298.5 MWh |
| Baseline cooling energy saved | 31.14 % |
| Annual energy cost savings | 155,820 $ |
| Annual grid emissions avoided | 454.48 t CO₂e |
Update the highlighted inputs to see the results.
Starting calculation
- Subtract 5 K of approach to get a 12 °C full-free cutoff. The entered bins give 3,500 full-free and 0 partial hours.
- Weight plant power by each bin. Annual cooling energy moves from 4,169.76 MWh to 2,871.26 MWh.
The zero-width band gives zero partial hours. At the cutoff, the bin qualifies for full-free mode.
Calculation method
- Full-free cutoff = applicable setpoint − total approach
- Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
- Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000
Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.
Engineering limits
ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.
Related worked examples
DataCenterPUELab · Calculation sheet
Waterside plant without partial operation
3,500 h of equivalent full-free cooling per year.
Inputs
- Economizer type
- Waterside · wet-bulb
- Inlet class
- ASHRAE A1
- IT inlet air setpoint
- 24 °C
- Chilled-water supply
- 17 °C
- Total approach
- 5 K
- Partial cooling band
- 0 K
- Plant cooling load
- 2461.7969894 kWₜₕ
- Mechanical plant input
- 0.1933546925476 kW/kWₜₕ
- Economizer plant input
- 0.04265177041491 kW/kWₜₕ
- Energy tariff
- 0.12 $/kWh
- Grid emissions factor
- 350 g/kWh
- Bin 1 temperature
- -3 °C
- Bin 1 hours
- 800 h
- Bin 2 temperature
- 5 °C
- Bin 2 hours
- 1200 h
- Bin 3 temperature
- 10 °C
- Bin 3 hours
- 1500 h
- Bin 4 temperature
- 15 °C
- Bin 4 hours
- 1800 h
- Bin 5 temperature
- 21 °C
- Bin 5 hours
- 1700 h
- Bin 6 temperature
- 28 °C
- Bin 6 hours
- 1760 h
Results
- Full-free outdoor cutoff
- 12 °C
- Mechanical cooling threshold
- 12 °C
- Full-free cooling hours
- 3,500 h
- Partial cooling hours
- 0 h
- Mechanical cooling hours
- 5,260 h
- Unentered hours assigned to mechanical
- 0 h
- Equivalent full-free cooling hours
- 3,500 h
- All-mechanical baseline energy
- 4,169.76 MWh
- Energy in full-free bins
- 367.5 MWh
- Energy in partial bins
- 0 MWh
- Energy in mechanical bins
- 2,503.76 MWh
- Modeled annual cooling energy
- 2,871.26 MWh
- Annual cooling energy savings
- 1,298.5 MWh
- Baseline cooling energy saved
- 31.14 %
- Annual energy cost savings
- 155,820 $
- Annual grid emissions avoided
- 454.48 t CO₂e
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.