High-elevation CRAH airflow

A 42 kW group at 1,650 m needs additional supply volume because the local air density is lower.

Engineering schematic

Sensible air path

Live
Sensible air path SUPPLY FLOW 4.63 m³/s. RACK ΔT 11 K. SENSIBLE 45 kW. DENSITY 0.983 kg/m³. See the results table for the full readout. SUPPLY FLOW4.63m³/sRACK ΔT11KSENSIBLE45kWDENSITY0.983kg/m³ CRAC/CRAH94% SHRHot returnCold aisle4.14 m³/s11 Krack rise10.7% delivery lossSensible load / rated sensible capacity0%80% usedLimit 100%

Sensible capacity headroom 11.4 kW

Inputs

Rack and cooling unit
kW
kW
kWₜₕ
%
Air path

Bypass and recirculation reduce the fraction of supply air that delivers effective rack cooling.

K
m
%
%

Calculation details

MeasureValue
Rack and room sensible load45 kW
Air density at site elevation0.9831 kg/m³
Effective delivery fraction89.28 %
Rack air temperature rise11 K
Useful rack airflow4.136 m³/s
Required or measured supply airflow4.633 m³/s
Airflow delivery penalty0.497 m³/s
Total coil duty at entered SHR47.87 kWₜₕ
Rated sensible coil capacity56.4 kWₜₕ
Rated latent coil capacity3.6 kWₜₕ
Sensible capacity headroom11.4 kW

Starting calculation

  1. Add IT and room heat for 45 kW sensible. The bypass and recirculation assumptions give 89.28% effective delivery.
  2. At 11 K and 0.983 kg/m³, the required fan supply is 4.633 m³/s (9,817 CFM).

Set the elevation to zero to isolate density from the other air-path effects.

Calculation method

  • Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
  • CFM ≈ 3.16 × W ÷ ΔT°F at reference density
  • Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]

Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.

Engineering limits

The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.