Low SHR leaves a sensible shortfall
A 48 kW total-capacity coil at 73% SHR serves a 41 kW sensible load. Assess nameplate headroom.
Engineering schematic
Sensible air path
Sensible capacity headroom -6 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Rack and room sensible load | 41 kW |
| Air density at site elevation | 1.2 kg/m³ |
| Effective delivery fraction | 83.72 % |
| Rack air temperature rise | 14 K |
| Useful rack airflow | 2.426 m³/s |
| Required or measured supply airflow | 2.898 m³/s |
| Airflow delivery penalty | 0.472 m³/s |
| Total coil duty at entered SHR | 56.16 kWₜₕ |
| Rated sensible coil capacity | 35.04 kWₜₕ |
| Rated latent coil capacity | 12.96 kWₜₕ |
| Sensible capacity headroom | -5.96 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Add IT and room heat for 41 kW sensible. The bypass and recirculation assumptions give 83.72% effective delivery.
- At 14 K and 1.2 kg/m³, the required fan supply is 2.898 m³/s (6,140 CFM).
Read the sensible capacity row before sizing airflow. The total nameplate includes latent cooling.
Calculation method
- Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
- CFM ≈ 3.16 × W ÷ ΔT°F at reference density
- Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]
Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.
Engineering limits
The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.
Related worked examples
DataCenterPUELab · Calculation sheet
Low SHR leaves a sensible shortfall
Sensible capacity headroom -6 kW
Inputs
- IT heat load
- 39 kW
- Other sensible heat
- 2 kW
- Total coil capacity
- 48 kWₜₕ
- Sensible heat ratio
- 73 %
- Calculate
- Supply airflow
- Target rack ΔT
- 14 K
- Site elevation
- 0 m
- Supply air bypass
- 9 %
- Hot air recirculation
- 8 %
Results
- Rack and room sensible load
- 41 kW
- Air density at site elevation
- 1.2 kg/m³
- Effective delivery fraction
- 83.72 %
- Rack air temperature rise
- 14 K
- Useful rack airflow
- 2.426 m³/s
- Required or measured supply airflow
- 2.898 m³/s
- Airflow delivery penalty
- 0.472 m³/s
- Total coil duty at entered SHR
- 56.16 kWₜₕ
- Rated sensible coil capacity
- 35.04 kWₜₕ
- Rated latent coil capacity
- 12.96 kWₜₕ
- Sensible capacity headroom
- -5.96 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.