DataCenterPUELab

Waterside plant without partial operation

The operating sequence is full-free or mechanical. The plant always switches over at one outdoor threshold.

Engineering schematic

Annual climate-bin dispatch

Live
Annual climate-bin dispatch FREE HOURS 3,500 h. ENERGY SAVE 1,298.5 MWh. COST SAVE 156k $. CO₂E AVOID 454.5 t CO₂e. See the results table for the full readout. FREE HOURS3,500hENERGY SAVE1,298.5MWhCOST SAVE156k$CO₂E AVOID454.5t CO₂e 800-3°1,2005°1,50010°1,80015°1,70021°1,76028°Full-freePartialMechanical°CEquivalent full-free cooling / year0%40% freeLimit 100%

3,500 h of equivalent full-free cooling per year.

Inputs

Operating limits
°C
°C
K
K
Load and utility rates
kWₜₕ
kW/kWₜₕ
kW/kWₜₕ
$/kWh
g/kWh
Annual climate bins

Enter six representative outdoor temperatures and annual hours. Any unentered hours, including lockouts, use mechanical cooling.

BinWet-bulbAnnual hours1
°C
h
2
°C
h
3
°C
h
4
°C
h
5
°C
h
6
°C
h

Calculation details

MeasureValue
Full-free outdoor cutoff12 °C
Mechanical cooling threshold12 °C
Full-free cooling hours3,500 h
Partial cooling hours0 h
Mechanical cooling hours5,260 h
Unentered hours assigned to mechanical0 h
Equivalent full-free cooling hours3,500 h
All-mechanical baseline energy4,169.76 MWh
Energy in full-free bins367.5 MWh
Energy in partial bins0 MWh
Energy in mechanical bins2,503.76 MWh
Modeled annual cooling energy2,871.26 MWh
Annual cooling energy savings1,298.5 MWh
Baseline cooling energy saved31.14 %
Annual energy cost savings155,820 $
Annual grid emissions avoided454.48 t CO₂e

Starting calculation

  1. Subtract 5 K of approach to get a 12 °C full-free cutoff. The entered bins give 3,500 full-free and 0 partial hours.
  2. Weight plant power by each bin. Annual cooling energy moves from 4,169.76 MWh to 2,871.26 MWh.

The zero-width band gives zero partial hours. At the cutoff, the bin qualifies for full-free mode.

Calculation method

  • Full-free cutoff = applicable setpoint − total approach
  • Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
  • Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000

Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.

Engineering limits

ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.