NFPA 20

Fire pump curve and driver sizing

Screen churn and 150% test points, estimate shaft load, and check suction and pressure maintenance.

Inputs

Measured net pump points
GPM
psi
psi
psi
psi
psi

Evaluate suction at the governing pump flow.

Driver and pressure maintenance
%
%
hp

Use 0 when the full-curve maximum is unavailable.

%
GPM
GPM
psi

Three-point fire pump curve

Worksheet units
Edit inputs
Three-point fire pump curve · Input-linked engineering diagramCHURN HEAD123%150% HEAD72%DRIVER LOAD102hpSUCTION MARGIN20psiHead · % of ratedTest pointsNFPA limits01002000100150Flow · % of ratedSmaller pump-curve reserve+7 pp−25 pp0 pp limit+25 pp
Curve and suction screens met

The three points and entered suction margin meet the screening criteria.

Calculated values

Churn · percent of rated pressure
123 %
150% flow · percent of rated pressure
72 %
150% test flow
1,500 GPM
Reserve below 140% ceiling
17 pp
Reserve above 65% floor
7 pp
Flowing suction reserve
20 psi
Rated water power
58.34 hp
150% water power
63.01 hp
Rated shaft load
81.03 hp
150% shaft load
94.05 hp
Electric mechanical power estimate
102 hp
Diesel pre-derating power estimate
113.33 hp
Pressure maintenance flow estimate
1.8 GPM
Jockey discharge target
161 psi

Equations and assumptions

  • Churn ≤ 140% of rated net pressure
  • P_150 ≥ 65% of rated net pressure
  • Water hp = Q ΔP / 1714
  • BHP = water hp / pump efficiency

Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.

The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.

The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.

Source references

Worked examples