NFPA 20 · Worked example

Diesel driver at a derated site

A 1,500 GPM, 118 psi pump has a 175 hp listed peak shaft load. The engine vendor specifies an 18% site derating.

Inputs

Measured net pump points
L/min
bar
bar
bar
bar
bar

Evaluate suction at the governing pump flow.

Driver and pressure maintenance
%
%
kW

Use 0 when the full-curve maximum is unavailable.

%
L/min
L/min
bar

Three-point fire pump curve

Worksheet units
Edit inputs
Three-point fire pump curve · Input-linked engineering diagramCHURN HEAD126.3%150% HEAD69.5%DRIVER LOAD130.5kWSUCTION MARGIN1.38barHead · % of ratedTest pointsNFPA limits01002000100150Flow · % of ratedSmaller pump-curve reserve+4.5 pp−25 pp0 pp limit+25 pp
Curve and suction screens met

The three points and entered suction margin meet the screening criteria.

How to read this example

Divide peak shaft load by the remaining 82% of nameplate capability. Compare that value with the uncorrected electric mechanical estimate.

Open the base calculator

Calculated values

Churn · percent of rated pressure
126.3 %
150% flow · percent of rated pressure
69.5 %
150% test flow
8,517.18 L/min
Reserve below 140% ceiling
13.7 pp
Reserve above 65% floor
4.5 pp
Flowing suction reserve
1.38 bar
Rated water power
77.01 kW
150% water power
80.27 kW
Rated shaft load
106.95 kW
150% shaft load
119.8 kW
Electric mechanical power estimate
130.5 kW
Diesel pre-derating power estimate
159.14 kW
Pressure maintenance flow estimate
6.81 L/min
Jockey discharge target
12.89 bar

Equations and assumptions

  • Churn ≤ 140% of rated net pressure
  • P_150 ≥ 65% of rated net pressure
  • Water hp = Q ΔP / 1714
  • BHP = water hp / pump efficiency

Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.

The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.

The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.