NFPA 20 · Worked example
Diesel driver at a derated site
A 1,500 GPM, 118 psi pump has a 175 hp listed peak shaft load. The engine vendor specifies an 18% site derating.
Inputs
Three-point fire pump curve
Edit inputsThe three points and entered suction margin meet the screening criteria.
How to read this example
Divide peak shaft load by the remaining 82% of nameplate capability. Compare that value with the uncorrected electric mechanical estimate.
Open the base calculatorCalculated values
- Churn · percent of rated pressure
- 126.3 %
- 150% flow · percent of rated pressure
- 69.5 %
- 150% test flow
- 8,517.18 L/min
- Reserve below 140% ceiling
- 13.7 pp
- Reserve above 65% floor
- 4.5 pp
- Flowing suction reserve
- 1.38 bar
- Rated water power
- 77.01 kW
- 150% water power
- 80.27 kW
- Rated shaft load
- 106.95 kW
- 150% shaft load
- 119.8 kW
- Electric mechanical power estimate
- 130.5 kW
- Diesel pre-derating power estimate
- 159.14 kW
- Pressure maintenance flow estimate
- 6.81 L/min
- Jockey discharge target
- 12.89 bar
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.