NFPA 20 · Worked example
Flowing suction below the project floor
A 1,250 GPM pump meets the head-envelope points, but effective suction during the governing test drops to 3 psi against a 10 psi floor.
Inputs
Three-point fire pump curve
Edit inputsMeasured flowing suction is below the entered minimum at the evaluated flow.
How to read this example
Report the suction pressure margin separately from the pump curve. Evaluate supply losses and available suction under the same flow condition.
Open the base calculatorCalculated values
- Churn · percent of rated pressure
- 123 %
- 150% flow · percent of rated pressure
- 70 %
- 150% test flow
- 1,875 GPM
- Reserve below 140% ceiling
- 17 pp
- Reserve above 65% floor
- 5 pp
- Flowing suction reserve
- -7 psi
- Rated water power
- 72.93 hp
- 150% water power
- 76.58 hp
- Rated shaft load
- 101.29 hp
- 150% shaft load
- 114.29 hp
- Electric mechanical power estimate
- 135 hp
- Diesel pre-derating power estimate
- 150 hp
- Pressure maintenance flow estimate
- 1.8 GPM
- Jockey discharge target
- 161 psi
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.