NFPA 20 · Worked example
Excess churn pressure
A 750 GPM pump is rated at 110 psi, but its observed net churn is 160 psi. The net 150% pressure is 80 psi.
Inputs
Three-point fire pump curve
Edit inputsOne or both fire-pump curve limits are outside the screening range.
How to read this example
Churn exceeds 140% of the rated net pressure even though the overload point clears its minimum. Check maximum static discharge with suction pressure included.
Open the base calculatorCalculated values
- Churn · percent of rated pressure
- 145.5 %
- 150% flow · percent of rated pressure
- 72.7 %
- 150% test flow
- 1,125 GPM
- Reserve below 140% ceiling
- -5.5 pp
- Reserve above 65% floor
- 7.7 pp
- Flowing suction reserve
- 20 psi
- Rated water power
- 48.13 hp
- 150% water power
- 52.51 hp
- Rated shaft load
- 66.85 hp
- 150% shaft load
- 78.37 hp
- Electric mechanical power estimate
- 100 hp
- Diesel pre-derating power estimate
- 111.11 hp
- Pressure maintenance flow estimate
- 1.8 GPM
- Jockey discharge target
- 198 psi
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.