NFPA 20 · Worked example

Low head at the 150% test point

A 1,500 GPM pump rated at 94 psi makes 58 psi net at 2,250 GPM. Its churn pressure is 120 psi.

Inputs

Measured net pump points
GPM
psi
psi
psi
psi
psi

Evaluate suction at the governing pump flow.

Driver and pressure maintenance
%
%
hp

Use 0 when the full-curve maximum is unavailable.

%
GPM
GPM
psi

Three-point fire pump curve

Worksheet units
Edit inputs
Three-point fire pump curve · Input-linked engineering diagramCHURN HEAD127.7%150% HEAD61.7%DRIVER LOAD145hpSUCTION MARGIN20psiHead · % of ratedTest pointsNFPA limits01002000100150Flow · % of ratedSmaller pump-curve reserve-3.3 pp−25 pp0 pp limit+25 pp
Curve points need review

One or both fire-pump curve limits are outside the screening range.

How to read this example

The overload head falls below 65% of rated net pressure. Calculate the difference in percentage points.

Open the base calculator

Calculated values

Churn · percent of rated pressure
127.7 %
150% flow · percent of rated pressure
61.7 %
150% test flow
2,250 GPM
Reserve below 140% ceiling
12.3 pp
Reserve above 65% floor
-3.3 pp
Flowing suction reserve
20 psi
Rated water power
82.26 hp
150% water power
76.14 hp
Rated shaft load
114.26 hp
150% shaft load
113.64 hp
Electric mechanical power estimate
145 hp
Diesel pre-derating power estimate
161.11 hp
Pressure maintenance flow estimate
1.8 GPM
Jockey discharge target
158 psi

Equations and assumptions

  • Churn ≤ 140% of rated net pressure
  • P_150 ≥ 65% of rated net pressure
  • Water hp = Q ΔP / 1714
  • BHP = water hp / pump efficiency

Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.

The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.

The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.