NFPA 20 · Worked example

Excess churn pressure

A 750 GPM pump is rated at 110 psi, but its observed net churn is 160 psi. The net 150% pressure is 80 psi.

Inputs

Measured net pump points
GPM
psi
psi
psi
psi
psi

Evaluate suction at the governing pump flow.

Driver and pressure maintenance
%
%
hp

Use 0 when the full-curve maximum is unavailable.

%
GPM
GPM
psi

Three-point fire pump curve

Worksheet units
Edit inputs
Three-point fire pump curve · Input-linked engineering diagramCHURN HEAD145.5%150% HEAD72.7%DRIVER LOAD100hpSUCTION MARGIN20psiHead · % of ratedTest pointsNFPA limits01002000100150Flow · % of ratedSmaller pump-curve reserve-5.5 pp−25 pp0 pp limit+25 pp
Curve points need review

One or both fire-pump curve limits are outside the screening range.

How to read this example

Churn exceeds 140% of the rated net pressure even though the overload point clears its minimum. Check maximum static discharge with suction pressure included.

Open the base calculator

Calculated values

Churn · percent of rated pressure
145.5 %
150% flow · percent of rated pressure
72.7 %
150% test flow
1,125 GPM
Reserve below 140% ceiling
-5.5 pp
Reserve above 65% floor
7.7 pp
Flowing suction reserve
20 psi
Rated water power
48.13 hp
150% water power
52.51 hp
Rated shaft load
66.85 hp
150% shaft load
78.37 hp
Electric mechanical power estimate
100 hp
Diesel pre-derating power estimate
111.11 hp
Pressure maintenance flow estimate
1.8 GPM
Jockey discharge target
198 psi

Equations and assumptions

  • Churn ≤ 140% of rated net pressure
  • P_150 ≥ 65% of rated net pressure
  • Water hp = Q ΔP / 1714
  • BHP = water hp / pump efficiency

Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.

The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.

The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.