NFPA 20
Fire pump curve and driver sizing
Screen churn and 150% test points, estimate shaft load, and check suction and pressure maintenance.
Inputs
Three-point fire pump curve
Edit inputsThe three points and entered suction margin meet the screening criteria.
Calculated values
- Churn · percent of rated pressure
- 123 %
- 150% flow · percent of rated pressure
- 72 %
- 150% test flow
- 1,500 GPM
- Reserve below 140% ceiling
- 17 pp
- Reserve above 65% floor
- 7 pp
- Flowing suction reserve
- 20 psi
- Rated water power
- 58.34 hp
- 150% water power
- 63.01 hp
- Rated shaft load
- 81.03 hp
- 150% shaft load
- 94.05 hp
- Electric mechanical power estimate
- 102 hp
- Diesel pre-derating power estimate
- 113.33 hp
- Pressure maintenance flow estimate
- 1.8 GPM
- Jockey discharge target
- 161 psi
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.