NFPA 20 · Worked example
Low head at the 150% test point
A 1,500 GPM pump rated at 94 psi makes 58 psi net at 2,250 GPM. Its churn pressure is 120 psi.
Inputs
Three-point fire pump curve
Edit inputsOne or both fire-pump curve limits are outside the screening range.
How to read this example
The overload head falls below 65% of rated net pressure. Calculate the difference in percentage points.
Open the base calculatorCalculated values
- Churn · percent of rated pressure
- 127.7 %
- 150% flow · percent of rated pressure
- 61.7 %
- 150% test flow
- 2,250 GPM
- Reserve below 140% ceiling
- 12.3 pp
- Reserve above 65% floor
- -3.3 pp
- Flowing suction reserve
- 20 psi
- Rated water power
- 82.26 hp
- 150% water power
- 76.14 hp
- Rated shaft load
- 114.26 hp
- 150% shaft load
- 113.64 hp
- Electric mechanical power estimate
- 145 hp
- Diesel pre-derating power estimate
- 161.11 hp
- Pressure maintenance flow estimate
- 1.8 GPM
- Jockey discharge target
- 158 psi
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.