NFPA 13 / 22 · Worked example

Diameter-limited tank site

A retrofit yard limits the available tank diameter to 17 ft. The design calls for 420 GPM sprinkler flow and 250 GPM hose flow for 60 minutes.

Inputs

Tank-fed demand
GPM
Proposed tank shell
ft
ft
%

Water below the effective low-water level.

%

Volume above the maximum operating water level.

Suction tank section

Worksheet units
Edit inputs
Suction tank section · Input-linked engineering diagramTANK DEMAND670GPMUSABLE TARGET40,200galGROSS TARGET45,681.82galRUN TIME46.83minFREEBOARD · 6%USABLE DRAWDOWN31,377.72 galLOW-WATER LEVELDead water 6%Ø 17 ftShell 21 ftAvailable vs. required duration-13.17 min0 min60 min target120 min
Usable storage shortfall

The entered shell cannot supply the selected fire demand for the full duration.

How to read this example

Use required height at the fixed diameter to see whether the chosen volume basis fits the available footprint.

Open the base calculator

Calculated values

Outside hose portion
200 GPM
Hose demand on this tank
250 GPM
Total tank-fed demand
670 GPM
Minimum usable storage
40,200 gal
Minimum gross shell volume
45,681.82 gal
Entered gross shell volume
35,656.51 gal
Entered usable drawdown
31,377.72 gal
Supply duration
46.83 min
Duration reserve
-13.17 min
Required height at entered diameter
26.9 ft
Required diameter at entered height
19.24 ft

Equations and assumptions

  • V_usable, required = (Q_sprinkler + Q_hose,tank) × t
  • V_gross = V_usable / (1 − dead fraction − freeboard fraction)
  • V_cylinder = π D² H / 4

Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.

Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.

The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.