NFPA 13 / 22 · Worked example
Diameter-limited tank site
A retrofit yard limits the available tank diameter to 17 ft. The design calls for 420 GPM sprinkler flow and 250 GPM hose flow for 60 minutes.
Inputs
Suction tank section
Edit inputsThe entered shell cannot supply the selected fire demand for the full duration.
How to read this example
Use required height at the fixed diameter to see whether the chosen volume basis fits the available footprint.
Open the base calculatorCalculated values
- Outside hose portion
- 200 GPM
- Hose demand on this tank
- 250 GPM
- Total tank-fed demand
- 670 GPM
- Minimum usable storage
- 40,200 gal
- Minimum gross shell volume
- 45,681.82 gal
- Entered gross shell volume
- 35,656.51 gal
- Entered usable drawdown
- 31,377.72 gal
- Supply duration
- 46.83 min
- Duration reserve
- -13.17 min
- Required height at entered diameter
- 26.9 ft
- Required diameter at entered height
- 19.24 ft
Equations and assumptions
V_usable, required = (Q_sprinkler + Q_hose,tank) × tV_gross = V_usable / (1 − dead fraction − freeboard fraction)V_cylinder = π D² H / 4
Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.
Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.