NFPA 13 / 22
Fire water tank sizing and duration
Combine sprinkler and hose demand, then size the usable drawdown and cylindrical tank shell.
Inputs
Suction tank section
Edit inputsUsable storage above the low-water limit covers the entered demand and duration.
Calculated values
- Outside hose portion
- 200 GPM
- Hose demand on this tank
- 250 GPM
- Total tank-fed demand
- 750 GPM
- Minimum usable storage
- 45,000 gal
- Minimum gross shell volume
- 50,561.8 gal
- Entered gross shell volume
- 51,184.62 gal
- Entered usable drawdown
- 45,554.31 gal
- Supply duration
- 60.74 min
- Duration reserve
- 0.74 min
- Required height at entered diameter
- 17.78 ft
- Required diameter at entered height
- 21.87 ft
Equations and assumptions
V_usable, required = (Q_sprinkler + Q_hose,tank) × tV_gross = V_usable / (1 − dead fraction − freeboard fraction)V_cylinder = π D² H / 4
Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.
Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.