NFPA 13 / 22 · Worked example

Two-hour supply with a shell shortfall

A high-demand system uses 1,750 GPM sprinkler flow plus 500 GPM hose allowance for a 120-minute storage basis.

Inputs

Tank-fed demand
GPM
Proposed tank shell
ft
ft
%

Water below the effective low-water level.

%

Volume above the maximum operating water level.

Suction tank section

Worksheet units
Edit inputs
Suction tank section · Input-linked engineering diagramTANK DEMAND2,250GPMUSABLE TARGET270,000galGROSS TARGET325,301.2galRUN TIME84.26minFREEBOARD · 5%USABLE DRAWDOWN189,594.61 galLOW-WATER LEVELDead water 12%Ø 36 ftShell 30 ftAvailable vs. required duration-35.74 min0 min120 min target240 min
Usable storage shortfall

The entered shell cannot supply the selected fire demand for the full duration.

How to read this example

Use both the required net capacity and the larger gross capacity when comparing alternative tanks.

Open the base calculator

Calculated values

Outside hose portion
400 GPM
Hose demand on this tank
500 GPM
Total tank-fed demand
2,250 GPM
Minimum usable storage
270,000 gal
Minimum gross shell volume
325,301.2 gal
Entered gross shell volume
228,427.24 gal
Entered usable drawdown
189,594.61 gal
Supply duration
84.26 min
Duration reserve
-35.74 min
Required height at entered diameter
42.72 ft
Required diameter at entered height
42.96 ft

Equations and assumptions

  • V_usable, required = (Q_sprinkler + Q_hose,tank) × t
  • V_gross = V_usable / (1 − dead fraction − freeboard fraction)
  • V_cylinder = π D² H / 4

Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.

Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.

The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.