NFPA 13 / 22 · Worked example
Two-hour supply with a shell shortfall
A high-demand system uses 1,750 GPM sprinkler flow plus 500 GPM hose allowance for a 120-minute storage basis.
Inputs
Suction tank section
Edit inputsThe entered shell cannot supply the selected fire demand for the full duration.
How to read this example
Use both the required net capacity and the larger gross capacity when comparing alternative tanks.
Open the base calculatorCalculated values
- Outside hose portion
- 400 GPM
- Hose demand on this tank
- 500 GPM
- Total tank-fed demand
- 2,250 GPM
- Minimum usable storage
- 270,000 gal
- Minimum gross shell volume
- 325,301.2 gal
- Entered gross shell volume
- 228,427.24 gal
- Entered usable drawdown
- 189,594.61 gal
- Supply duration
- 84.26 min
- Duration reserve
- -35.74 min
- Required height at entered diameter
- 42.72 ft
- Required diameter at entered height
- 42.96 ft
Equations and assumptions
V_usable, required = (Q_sprinkler + Q_hose,tank) × tV_gross = V_usable / (1 − dead fraction − freeboard fraction)V_cylinder = π D² H / 4
Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.
Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.