NFPA 13 / 22 · Worked example
30-minute light-hazard water supply
The tank supplies 135 GPM sprinkler demand and 100 GPM combined hose allowance for the selected 30 minutes.
Inputs
Suction tank section
Edit inputsUsable storage above the low-water limit covers the entered demand and duration.
How to read this example
Size the usable drawdown first. The shell also accommodates dead water and freeboard.
Open the base calculatorCalculated values
- Outside hose portion
- 100 GPM
- Hose demand on this tank
- 100 GPM
- Total tank-fed demand
- 235 GPM
- Minimum usable storage
- 7,050 gal
- Minimum gross shell volume
- 8,103.45 gal
- Entered gross shell volume
- 9,306.3 gal
- Entered usable drawdown
- 8,096.48 gal
- Supply duration
- 34.45 min
- Duration reserve
- 4.45 min
- Required height at entered diameter
- 9.58 ft
- Required diameter at entered height
- 11.2 ft
Equations and assumptions
V_usable, required = (Q_sprinkler + Q_hose,tank) × tV_gross = V_usable / (1 − dead fraction − freeboard fraction)V_cylinder = π D² H / 4
Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.
Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.