NFPA 13 / 22 · Worked example
Separate outside hose supply
A 660 GPM sprinkler demand and 50 GPM inside hose portion draw from storage. A verified fire-water source takes the outside portion.
Inputs
Suction tank section
Edit inputsUsable storage above the low-water limit covers the entered demand and duration.
How to read this example
Compare the separate-source assumption with running all hose demand through the tank. The total hose allocation remains visible.
Open the base calculatorCalculated values
- Outside hose portion
- 757.08 L/min
- Hose demand on this tank
- 189.27 L/min
- Total tank-fed demand
- 2,687.64 L/min
- Minimum usable storage
- 241.89 m³
- Minimum gross shell volume
- 271.78 m³
- Entered gross shell volume
- 278 m³
- Entered usable drawdown
- 247.42 m³
- Supply duration
- 92.06 min
- Duration reserve
- 2.06 min
- Required height at entered diameter
- 5.96 m
- Required diameter at entered height
- 7.53 m
Equations and assumptions
V_usable, required = (Q_sprinkler + Q_hose,tank) × tV_gross = V_usable / (1 − dead fraction − freeboard fraction)V_cylinder = π D² H / 4
Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.
Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.