NFPA 13 / 22 · Worked example

30-minute light-hazard water supply

The tank supplies 135 GPM sprinkler demand and 100 GPM combined hose allowance for the selected 30 minutes.

Inputs

Tank-fed demand
GPM
Proposed tank shell
ft
ft
%

Water below the effective low-water level.

%

Volume above the maximum operating water level.

Suction tank section

Worksheet units
Edit inputs
Suction tank section · Input-linked engineering diagramTANK DEMAND235GPMUSABLE TARGET7,050galGROSS TARGET8,103.45galRUN TIME34.45minFREEBOARD · 5%USABLE DRAWDOWN8,096.48 galLOW-WATER LEVELDead water 8%Ø 12 ftShell 11 ftAvailable vs. required duration+4.45 min0 min30 min target60 min
Water duration target met

Usable storage above the low-water limit covers the entered demand and duration.

How to read this example

Size the usable drawdown first. The shell also accommodates dead water and freeboard.

Open the base calculator

Calculated values

Outside hose portion
100 GPM
Hose demand on this tank
100 GPM
Total tank-fed demand
235 GPM
Minimum usable storage
7,050 gal
Minimum gross shell volume
8,103.45 gal
Entered gross shell volume
9,306.3 gal
Entered usable drawdown
8,096.48 gal
Supply duration
34.45 min
Duration reserve
4.45 min
Required height at entered diameter
9.58 ft
Required diameter at entered height
11.2 ft

Equations and assumptions

  • V_usable, required = (Q_sprinkler + Q_hose,tank) × t
  • V_gross = V_usable / (1 − dead fraction − freeboard fraction)
  • V_cylinder = π D² H / 4

Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.

Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.

The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.