NFPA 13 / 22 · Worked example

Separate outside hose supply

A 660 GPM sprinkler demand and 50 GPM inside hose portion draw from storage. A verified fire-water source takes the outside portion.

Inputs

Tank-fed demand
L/min
Proposed tank shell
m
m
%

Water below the effective low-water level.

%

Volume above the maximum operating water level.

Suction tank section

Worksheet units
Edit inputs
Suction tank section · Input-linked engineering diagramTANK DEMAND2,687.64L/minUSABLE TARGET241.89m³GROSS TARGET271.78m³RUN TIME92.06minFREEBOARD · 4%USABLE DRAWDOWN247.42 m³LOW-WATER LEVELDead water 7%Ø 7.62 mShell 6.1 mAvailable vs. required duration+2.06 min0 min90 min target180 min
Water duration target met

Usable storage above the low-water limit covers the entered demand and duration.

How to read this example

Compare the separate-source assumption with running all hose demand through the tank. The total hose allocation remains visible.

Open the base calculator

Calculated values

Outside hose portion
757.08 L/min
Hose demand on this tank
189.27 L/min
Total tank-fed demand
2,687.64 L/min
Minimum usable storage
241.89 m³
Minimum gross shell volume
271.78 m³
Entered gross shell volume
278 m³
Entered usable drawdown
247.42 m³
Supply duration
92.06 min
Duration reserve
2.06 min
Required height at entered diameter
5.96 m
Required diameter at entered height
7.53 m

Equations and assumptions

  • V_usable, required = (Q_sprinkler + Q_hose,tank) × t
  • V_gross = V_usable / (1 − dead fraction − freeboard fraction)
  • V_cylinder = π D² H / 4

Select the allowance and duration required by the adopted sprinkler design basis. Count outside hose demand on this tank unless a separate supply can deliver that portion.

Gross volume is the straight cylindrical shell. Usable storage lies between the maximum operating level and the effective low-water level above the suction intake or vortex assembly.

The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.