NFPA 291
Hydrant flow test and supply curve
Convert flowing pitot readings to total test flow and compare the N¹·⁸⁵ supply curve with a system demand point.
Inputs
Water supply curve
Edit inputsPredicted pressure at demand flow meets the entered pressure at the test datum.
Calculated values
- First group · flow per outlet
- 822.29 GPM
- Second group · flow per outlet
- 0 GPM
- Total measured flow
- 822.29 GPM
- Measured residual drop
- 18 psi
- Measured pressure drop
- 25 %
- Reference flow at 20 psi / 1.38 bar
- 1,458.22 GPM
- Supply pressure at demand flow
- 48.49 psi
- Pressure margin at demand flow
- 3.49 psi
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.