NFPA 291

Hydrant flow test and supply curve

Convert flowing pitot readings to total test flow and compare the N¹·⁸⁵ supply curve with a system demand point.

Inputs

Flowing outlets
in
psi
Pressure hydrant and demand
psi
psi

Read static and flowing residual at the same monitor hydrant.

GPM
psi

Use the test gauge elevation datum.

Water supply curve

Worksheet units
Edit inputs
Water supply curve · Input-linked engineering diagramTEST FLOW822.29GPM20 PSI FLOW1,458.22GPMSUPPLY HEAD48.49psiHEAD RESERVE3.49psiPressure · psiSupply curveDemand point05010001,0002,000Flow · GPMSupply vs. demand pressure+3.49 psi0 psi45 psi target90 psi
Demand point below supply

Predicted pressure at demand flow meets the entered pressure at the test datum.

Calculated values

First group · flow per outlet
822.29 GPM
Second group · flow per outlet
0 GPM
Total measured flow
822.29 GPM
Measured residual drop
18 psi
Measured pressure drop
25 %
Reference flow at 20 psi / 1.38 bar
1,458.22 GPM
Supply pressure at demand flow
48.49 psi
Pressure margin at demand flow
3.49 psi

Equations and assumptions

  • Q_outlet = 29.84 c d² √P_pitot
  • Q_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴
  • P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵

The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.

Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.

Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.

Source references

Worked examples