NFPA 291 · Worked example
Mixed bore and outlet profile
One 2½ in. rounded outlet and two 2 in. projecting outlets flow together. Their pitot readings are 21 and 16 psi, respectively.
Inputs
Water supply curve
Edit inputsPredicted pressure at demand flow meets the entered pressure at the test datum.
How to read this example
Keep the profiles and pitot readings in separate groups. The SVG uses the summed discharge at the common measured residual.
Open the base calculatorCalculated values
- First group · flow per outlet
- 2,911.68 L/min
- Second group · flow per outlet
- 1,265.11 L/min
- Total measured flow
- 5,441.91 L/min
- Measured residual drop
- 1.65 bar
- Measured pressure drop
- 34.8 %
- Reference flow at 20 psi / 1.38 bar
- 8,000.98 L/min
- Supply pressure at demand flow
- 3.52 bar
- Pressure margin at demand flow
- 0.97 bar
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.