NFPA 291 · Worked example

Two matching flowing outlets

Two 2½ in. rounded outlets each show 18 psi pitot. A separate gauge shows a 78 psi static reading and a 53 psi residual reading.

Inputs

Flowing outlets
in
psi
Pressure hydrant and demand
psi
psi

Read static and flowing residual at the same monitor hydrant.

GPM
psi

Use the test gauge elevation datum.

Water supply curve

Worksheet units
Edit inputs
Water supply curve · Input-linked engineering diagramTEST FLOW1,424.25GPM20 PSI FLOW2,243.63GPMSUPPLY HEAD47psiHEAD RESERVE3psiPressure · psiSupply curveDemand point05010002,5005,000Flow · GPMSupply vs. demand pressure+3 psi0 psi44 psi target88 psi
Demand point below supply

Predicted pressure at demand flow meets the entered pressure at the test datum.

How to read this example

The test flow is the sum of both outlets. The monitor gauge still supplies one static/residual pair for the curve.

Open the base calculator

Calculated values

First group · flow per outlet
712.13 GPM
Second group · flow per outlet
0 GPM
Total measured flow
1,424.25 GPM
Measured residual drop
25 psi
Measured pressure drop
32.1 %
Reference flow at 20 psi / 1.38 bar
2,243.63 GPM
Supply pressure at demand flow
47 psi
Pressure margin at demand flow
3 psi

Equations and assumptions

  • Q_outlet = 29.84 c d² √P_pitot
  • Q_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴
  • P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵

The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.

Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.

Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.

Source references

Related examples