NFPA 291 · Worked example
Two matching flowing outlets
Two 2½ in. rounded outlets each show 18 psi pitot. A separate gauge shows a 78 psi static reading and a 53 psi residual reading.
Inputs
Water supply curve
Edit inputsPredicted pressure at demand flow meets the entered pressure at the test datum.
How to read this example
The test flow is the sum of both outlets. The monitor gauge still supplies one static/residual pair for the curve.
Open the base calculatorCalculated values
- First group · flow per outlet
- 712.13 GPM
- Second group · flow per outlet
- 0 GPM
- Total measured flow
- 1,424.25 GPM
- Measured residual drop
- 25 psi
- Measured pressure drop
- 32.1 %
- Reference flow at 20 psi / 1.38 bar
- 2,243.63 GPM
- Supply pressure at demand flow
- 47 psi
- Pressure margin at demand flow
- 3 psi
Equations and assumptions
Q_outlet = 29.84 c d² √P_pitotQ_20 = Q_test [(P_static − 20)/(P_static − P_residual)]⁰·⁵⁴P(Q) = P_static − (P_static − P_residual)(Q/Q_test)¹·⁸⁵
The 20 psi result uses the rounded 0.54 exponent. The plotted pressure curve uses 1.85. Predicted pressure at demand is floored at zero beyond the curve intercept.
Group identical outlets together and add unlike readings as a second group. Outlet coefficients describe outlet geometry. Check the additional test provisions for pumper outlets, devices and unusual geometry.
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.