NFPA 13 · Worked example

Copper drop serving a lower sprinkler

A copper tube with 1.055 in. bore carries 23 GPM. The final outlet is 15 ft down from the segment inlet.

Inputs

Pipe and roughness
in

Use the product submittal or a measured bore.

Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP-2.92psiOUTLET34.92psiVELOCITY8.44ft/sPIPE BORE1.055inIN 32 psiOUT 34.92 psiC 150 · ID 1.055 inEq. 33 ftVelocity vs. project limit+6.56 ft/s0 ft/s15 ft/s target30 ft/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

How to read this example

The elevation term adds pressure at the outlet. Compare its magnitude with the friction subtotal to see the net effect.

Open the base calculator

Calculated values

Net segment pressure drop
-2.92 psi
Predicted outlet pressure
34.92 psi
Mean water velocity
8.44 ft/s
Velocity headroom
6.56 ft/s
Internal pipe diameter
1.055 in
Hazen–Williams C
150
Friction gradient
0.10847 psi/ft
Total equivalent length
33 ft
Straight-pipe loss
2.6 psi
Fitting loss
0.98 psi
Friction subtotal
3.58 psi
Signed elevation loss
-6.5 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Related examples