NFPA 13
Sprinkler pipe friction and velocity
Separate straight-pipe, fitting and elevation losses in one sprinkler branch or main.
Inputs
Branch pressure section
Edit inputsVelocity is within the entered limit. Use outlet pressure in the next hydraulic segment.
Calculated values
- Net segment pressure drop
- 18.31 psi
- Predicted outlet pressure
- 56.69 psi
- Mean water velocity
- 8.83 ft/s
- Velocity headroom
- 6.17 ft/s
- Internal pipe diameter
- 2.635 in
- Hazen–Williams C
- 120
- Friction gradient
- 0.06098 psi/ft
- Total equivalent length
- 215 ft
- Straight-pipe loss
- 10.98 psi
- Fitting loss
- 2.13 psi
- Friction subtotal
- 13.11 psi
- Signed elevation loss
- 5.2 psi
Equations and assumptions
p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷ΔP = p (L + L_eq) + 0.433 Δzv = Q / cross-sectional area
The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.
Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.
Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.