NFPA 13

Sprinkler pipe friction and velocity

Separate straight-pipe, fitting and elevation losses in one sprinkler branch or main.

Inputs

Pipe and roughness
Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP18.31psiOUTLET56.69psiVELOCITY8.83ft/sPIPE BORE2.635inIN 75 psiOUT 56.69 psiC 120 · ID 2.635 inEq. 215 ftVelocity vs. project limit+6.17 ft/s0 ft/s15 ft/s target30 ft/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

Calculated values

Net segment pressure drop
18.31 psi
Predicted outlet pressure
56.69 psi
Mean water velocity
8.83 ft/s
Velocity headroom
6.17 ft/s
Internal pipe diameter
2.635 in
Hazen–Williams C
120
Friction gradient
0.06098 psi/ft
Total equivalent length
215 ft
Straight-pipe loss
10.98 psi
Fitting loss
2.13 psi
Friction subtotal
13.11 psi
Signed elevation loss
5.2 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Worked examples