NFPA 13 · Worked example

Downhill Schedule 40 feed

A wet NPS 5 feed transfers 520 GPM to an outlet 35 ft below the inlet. The straight and equivalent fitting runs total 295 ft.

Inputs

Pipe and roughness
Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP-7.58psiOUTLET102.58psiVELOCITY8.34ft/sPIPE BORE5.047inIN 95 psiOUT 102.58 psiC 120 · ID 5.047 inEq. 295 ftVelocity vs. project limit+6.66 ft/s0 ft/s15 ft/s target30 ft/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

How to read this example

A negative net pressure drop indicates a gain in this steady segment. Use the resulting pressure in the adjacent path calculation.

Open the base calculator

Calculated values

Net segment pressure drop
-7.58 psi
Predicted outlet pressure
102.58 psi
Mean water velocity
8.34 ft/s
Velocity headroom
6.66 ft/s
Internal pipe diameter
5.047 in
Hazen–Williams C
120
Friction gradient
0.02567 psi/ft
Total equivalent length
295 ft
Straight-pipe loss
6.42 psi
Fitting loss
1.16 psi
Friction subtotal
7.57 psi
Signed elevation loss
-15.16 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Related examples