NFPA 13 · Worked example
Measured bore on a remodeled main
The existing wet main has a 3.89 in. measured bore where the project schedule is uncertain. It carries 450 GPM at an 82 psi inlet.
Inputs
Branch pressure section
Edit inputsVelocity is within the entered limit. Use outlet pressure in the next hydraulic segment.
How to read this example
Use the custom bore. The pressure predictions describe the entered main at a specified flow, then the network calculation allocates flow across its parallel paths.
Open the base calculatorCalculated values
- Net segment pressure drop
- 34.37 psi
- Predicted outlet pressure
- 47.63 psi
- Mean water velocity
- 12.15 ft/s
- Velocity headroom
- 2.85 ft/s
- Internal pipe diameter
- 3.89 in
- Hazen–Williams C
- 120
- Friction gradient
- 0.06983 psi/ft
- Total equivalent length
- 455 ft
- Straight-pipe loss
- 26.19 psi
- Fitting loss
- 5.59 psi
- Friction subtotal
- 31.77 psi
- Signed elevation loss
- 2.6 psi
Equations and assumptions
p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷ΔP = p (L + L_eq) + 0.433 Δzv = Q / cross-sectional area
The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.
Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.
Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.