NFPA 13 · Worked example

Measured bore on a remodeled main

The existing wet main has a 3.89 in. measured bore where the project schedule is uncertain. It carries 450 GPM at an 82 psi inlet.

Inputs

Pipe and roughness
in

Use the product submittal or a measured bore.

Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP34.37psiOUTLET47.63psiVELOCITY12.15ft/sPIPE BORE3.89inIN 82 psiOUT 47.63 psiC 120 · ID 3.89 inEq. 455 ftVelocity vs. project limit+2.85 ft/s0 ft/s15 ft/s target30 ft/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

How to read this example

Use the custom bore. The pressure predictions describe the entered main at a specified flow, then the network calculation allocates flow across its parallel paths.

Open the base calculator

Calculated values

Net segment pressure drop
34.37 psi
Predicted outlet pressure
47.63 psi
Mean water velocity
12.15 ft/s
Velocity headroom
2.85 ft/s
Internal pipe diameter
3.89 in
Hazen–Williams C
120
Friction gradient
0.06983 psi/ft
Total equivalent length
455 ft
Straight-pipe loss
26.19 psi
Fitting loss
5.59 psi
Friction subtotal
31.77 psi
Signed elevation loss
2.6 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references