NFPA 13 · Worked example

Dry steel run in cold storage

An NPS 3 steel run sees 240 GPM over 170 straight feet. Use the usual C = 100 baseline for an air-supervised dry system.

Inputs

Pipe and roughness
Hydraulic path
GPM
psi
ft
ft
ft

A negative number represents a downhill run.

ft/s

Branch pressure section

Worksheet units
Edit inputs
Branch pressure section · Input-linked engineering diagramNET DROP26.9psiOUTLET63.1psiVELOCITY10.42ft/sPIPE BORE3.068inIN 90 psiOUT 63.1 psiC 100 · ID 3.068 inEq. 210 ftVelocity vs. project limit+4.58 ft/s0 ft/s15 ft/s target30 ft/s
Within velocity screen

Velocity is within the entered limit. Use outlet pressure in the next hydraulic segment.

How to read this example

Compare with the wet steel setting to isolate the effect of C on friction at fixed flow and bore.

Open the base calculator

Calculated values

Net segment pressure drop
26.9 psi
Predicted outlet pressure
63.1 psi
Mean water velocity
10.42 ft/s
Velocity headroom
4.58 ft/s
Internal pipe diameter
3.068 in
Hazen–Williams C
100
Friction gradient
0.09717 psi/ft
Total equivalent length
210 ft
Straight-pipe loss
16.52 psi
Fitting loss
3.89 psi
Friction subtotal
20.41 psi
Signed elevation loss
6.5 psi

Equations and assumptions

  • p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷
  • ΔP = p (L + L_eq) + 0.433 Δz
  • v = Q / cross-sectional area

The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.

Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.

Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.

Source references

Related examples