NFPA 13 · Worked example
Dry steel run in cold storage
An NPS 3 steel run sees 240 GPM over 170 straight feet. Use the usual C = 100 baseline for an air-supervised dry system.
Inputs
Branch pressure section
Edit inputsVelocity is within the entered limit. Use outlet pressure in the next hydraulic segment.
How to read this example
Compare with the wet steel setting to isolate the effect of C on friction at fixed flow and bore.
Open the base calculatorCalculated values
- Net segment pressure drop
- 26.9 psi
- Predicted outlet pressure
- 63.1 psi
- Mean water velocity
- 10.42 ft/s
- Velocity headroom
- 4.58 ft/s
- Internal pipe diameter
- 3.068 in
- Hazen–Williams C
- 100
- Friction gradient
- 0.09717 psi/ft
- Total equivalent length
- 210 ft
- Straight-pipe loss
- 16.52 psi
- Fitting loss
- 3.89 psi
- Friction subtotal
- 20.41 psi
- Signed elevation loss
- 6.5 psi
Equations and assumptions
p = 4.52 (Q/C)¹·⁸⁵ / d⁴·⁸⁷ΔP = p (L + L_eq) + 0.433 Δzv = Q / cross-sectional area
The U.S. equation uses GPM, actual internal diameter in inches and equivalent length in feet. The pressure gradient is in psi per foot.
Enter fitting lengths for the actual sizes, valves and C-factor. C = 100 is the conventional dry/preaction steel selection. Confirm permitted alternatives for the installed system.
Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.