NFPA 14 · Worked example

Static pressure flags the lower zone

A 14-floor riser has 211 psi maximum static at the base. Its top connection is 160 ft above the datum.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

ft
psi
psi

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW1,000GPMSTATIC RISE69.28psiBASE RESIDUAL179.28psiPRV FLOORS7FLOOR 14FLOOR 1TOP OUTLET100 psi flowingPRV REVIEWF1–F7BASE MAXIMUM211 psiHighest outlet vs. 175 psi screen-36 psi0 psi175 psi target350 psi
Review the pressure zone

The outlet schedule flags static or modeled residual pressure above 175 psi.

How to read this example

Open the pressure schedule to identify where static first drops to 175 psi or below. Verify the listed valve range at actual flow.

Open the base calculator

Calculated values

Class I demand after cap
1,000 GPM
Flow before cap
1,000 GPM
Applied flow cap
1,000 GPM
Elevation head to top outlet
69.28 psi
Required base residual
179.28 psi
Estimated top static
141.72 psi
Governing base outlet pressure
211 psi
Reserve below outlet pressure ceiling
-36 psi
Floors flagged for pressure review
7
First floor within pressure screen
8
Outlet pressure by floor 14 rows
Outlet pressure by floor
FloorRiseftStaticpsiFlowingpsiPRV review
10211179.3Both
212.3205.7173.2Static
324.6200.3167.1Static
436.9195161Static
549.2189.7154.9Static
661.5184.4148.8Static
773.8179142.7Static
886.2173.7136.6Clear
998.5168.4130.5Clear
10110.8163124.4Clear
11123.1157.7118.3Clear
12135.4152.4112.2Clear
13147.7147106.1Clear
14160141.7100Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.