NFPA 14 · Worked example

Flowing base requirement governs zoning

The top outlet is 210 ft up, and the entered flowing loss is 32 psi. The entered maximum base static is lower than the inferred flowing base requirement.

Inputs

Demand basis
Riser geometry and pressure

One representative outlet per floor.

ft
psi
psi

Class I riser elevation

Worksheet units
Edit inputs
Class I riser elevation · Input-linked engineering diagramCLASS I FLOW750GPMSTATIC RISE90.93psiBASE RESIDUAL222.93psiPRV FLOORS8FLOOR 19FLOOR 1TOP OUTLET100 psi flowingPRV REVIEWF1–F8BASE MAXIMUM222.93 psiHighest outlet vs. 175 psi screen-47.93 psi0 psi175 psi target350 psi
Review the pressure zone

The outlet schedule flags static or modeled residual pressure above 175 psi. Entered static is also below the required flowing base pressure.

How to read this example

The schedule flags the flowing profile. Reconcile static and flowing basis before using the output as a zoning input.

Open the base calculator

Calculated values

Class I demand after cap
750 GPM
Flow before cap
750 GPM
Applied flow cap
1,000 GPM
Elevation head to top outlet
90.93 psi
Required base residual
222.93 psi
Estimated top static
79.07 psi
Governing base outlet pressure
222.93 psi
Reserve below outlet pressure ceiling
-47.93 psi
Floors flagged for pressure review
8
First floor within pressure screen
9
Outlet pressure by floor 19 rows
Outlet pressure by floor
FloorRiseftStaticpsiFlowingpsiPRV review
10170222.9Flowing
211.7164.9216.1Flowing
323.3159.9209.3Flowing
435154.8202.4Flowing
546.7149.8195.6Flowing
658.3144.7188.8Flowing
770139.7182Flowing
881.7134.6175.1Flowing
993.3129.6168.3Clear
10105124.5161.5Clear
11116.7119.5154.6Clear
12128.3114.4147.8Clear
13140109.4141Clear
14151.7104.3134.1Clear
15163.399.3127.3Clear
1617594.2120.5Clear
17186.789.2113.7Clear
18198.384.1106.8Clear
1921079.1100Clear

Equations and assumptions

  • Q = min(500 + 250 (n − 1), 1000 or 1250 GPM)
  • P_base,flowing = 100 psi + 0.433 Δz + friction
  • P_static at floor = P_base,static − 0.433 × floor rise

This is the common vertical Class I demand basis. The remote 2½-inch outlet target is 100 psi residual. Special layouts, large floor areas and combined-system criteria can change the flow basis.

The floor schedule assumes evenly spaced outlets and prorates the entered flowing loss by elevation. A floor is flagged if static or modeled residual exceeds 175 psi. Verify listed pressure regulation using the available inlet static and residual, valve ratings and the adopted edition.

Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.