API 521 · Restriction orifice
Blowdown with a nozzle-regime crossover
A gas vessel vents from 3,100 kPa(a) toward 700 kPa(a) into a 620 kPa(a) header.
The nozzle is choked early and becomes subsonic as the vessel approaches header pressure.
Operating readout
Edit inputs ↓- Time to target
- 5.12min
- Peak flow
- 6,793.91kg/h
- Min. gas temp
- -47.01°C
- 15-min RO ID
- 14.022mm
Calculated details
- Selected absolute target
- 700kPa(a)
- Initial vapor inventory
- 442.6kg
- Choked/subsonic transition pressure
- 1,128.57kPa(a)
- Transition time if crossed
- 3.26min
- Starting regime
- Choked
- Target regime
- Subsonic
- Minimum gas temperature above MDMT
- -18.01K
Operating inputs
Operating inputs
- Vessel gas volume
- 18m³
- Initial pressure P₀
- 31bar(a)
- Initial temperature
- 40°C
- Outlet backpressure
- 620kPa(a)
- Target pressure basis
- Custom absolute pressure
- Target pressure
- 700kPa(a)
- Vessel thermal model
- Adiabatic
- Minimum metal temperature
- -29°C
- Orifice diameter
- 24mm
- Discharge coefficient Cd
- 0.72
- Specific heat ratio k
- 1.28
- Molecular weight
- 19kg/kmol
- Vessel compressibility Z
- 0.92
Calculated details
- Selected absolute target
- 700kPa(a)
- Initial vapor inventory
- 442.6kg
- Choked/subsonic transition pressure
- 1,128.57kPa(a)
- Transition time if crossed
- 3.26min
- Starting regime
- Choked
- Target regime
- Subsonic
- Minimum gas temperature above MDMT
- -18.01K
The selectable 50% target uses initial absolute pressure. API 521 fire depressuring guidance commonly references 50% of vessel design pressure in about 15 minutes in its applicable scenario. About 6.9 barg in 15 minutes is another commonly used consequence-reduction screen. Confirm the design target, flare network backpressure, heat input, vapor–liquid behavior, wall temperature and stress before approval.
Calculation basis
Inventory and discharge
Use a uniform vapor inventory with fixed Z and k. Pressure follows mass to the power k for adiabatic operation, or mass directly for isothermal operation. Compute instantaneous gas flux with the choked expression below the critical backpressure ratio and the subsonic nozzle expression above it.
Integrate time
Integrate dM/ṁ down to the selected pressure with a transformed pressure coordinate. Solve the 15-minute orifice diameter using the inverse-area time scaling for this model.
Related worked examples
-
Separator fire depressuring screen →
A 64 m³ vapor inventory depressures adiabatically toward half of initial absolute pressure.
-
Compressor suction scrubber depressuring →
A gas scrubber is screened to nominal 100 psig with the isothermal inventory option.
-
Target just above header pressure →
An inventory screen approaches 413 kPa(a) with a fixed 410 kPa(a) receiving header.
-
Cold gas inventory blowdown →
A cold methane-rich vessel starts at 6 °C before adiabatic depressuring to 6.9 barg.
-
Small restriction orifice retrofit →
An existing 11 mm restriction is compared with a 15-minute depressuring target for a 44 m³ vapor volume.