GasCompressLab

API 521 · Restriction orifice

Blowdown with a nozzle-regime crossover

A gas vessel vents from 3,100 kPa(a) toward 700 kPa(a) into a 620 kPa(a) header.

What to check

The nozzle is choked early and becomes subsonic as the vessel approaches header pressure.

Operating readout

Edit inputs ↓
Time to target
5.12min
Peak flow
6,793.91kg/h
Min. gas temp
-47.01°C
15-min RO ID
14.022mm
Cold blowdown below MDMTThe calculated minimum gas temperature is below the entered metal temperature screen.
Vessel blowdown pressure and mass-flow decayVESSEL / RESTRICTION / HEADERmmGas inventoryRO 24DEPRESSURINGP · kPa(a)Flow · kg/h3100700679000 min15.6 min15-MINUTE SCREEN5.12 min
Pressure and mass flow use independent scales. The vertical gate marks 15 minutes, and the plotted curves end at the selected pressure target.
Calculated details
Selected absolute target
700kPa(a)
Initial vapor inventory
442.6kg
Choked/subsonic transition pressure
1,128.57kPa(a)
Transition time if crossed
3.26min
Starting regime
Choked
Target regime
Subsonic
Minimum gas temperature above MDMT
-18.01K

Operating inputs

Vessel and target
m³
bar(a)
°C
kPa(a)
kPa(a)
°C
Restriction and gas
mm
kg/kmol

Calculation basis

Inventory and discharge

Use a uniform vapor inventory with fixed Z and k. Pressure follows mass to the power k for adiabatic operation, or mass directly for isothermal operation. Compute instantaneous gas flux with the choked expression below the critical backpressure ratio and the subsonic nozzle expression above it.

Integrate time

Integrate dM/ṁ down to the selected pressure with a transformed pressure coordinate. Solve the 15-minute orifice diameter using the inverse-area time scaling for this model.