Worked example
Circular footing with water at its base
A circular equipment pad has a centered vertical load and groundwater at founding level.
Results
Edit inputs ↓- Allowable
- 359.8 kPa
- Ultimate
- 1,079.4 kPa
- Overburden
- 21.6 kPa
- Eff. width
- 2.1 m
- Bearing wedge
- Groundwater
- Footing base
Applied pressure is within the gross bearing screen.
Calculation details
| Allowable minus applied | 174.8 kPa |
|---|---|
| Wedge effective unit weight γeff | 10.19 kN/m³ |
| Cohesion factor Nc | 34.242 |
| Overburden factor Nq | 19.981 |
| Unit-weight factor Nγ | 17.7 |
| Cohesion contribution | 534.2 kPa |
| Overburden contribution | 431.6 kPa |
| Soil wedge contribution | 113.7 kPa |
| Width after eccentricity B′ | 2.1 m |
| Length after eccentricity L′ | 2.1 m |
| Cohesion / surcharge inclination factor | 1 |
| Wedge inclination factor | 1 |
| Effective plan area | 3.46 m² |
| Gross allowable load | 1,246.2 kN |
GeotechSoilLab · Screening sheet · Metric SI
Circular footing with water at its base
| Bearing method | Terzaghi |
|---|---|
| Footing shape | Circle |
| Width or diameter B | 2.1 m |
| Base depth Df | 1.2 m |
| Cohesion c′ | 12 kPa |
| Friction angle φ′ | 29 ° |
| Moist weight γ | 18 kN/m³ |
| Saturated weight γsat | 20 kN/m³ |
| Water table depth Dw | 1.2 m |
| Bearing safety factor | 3 |
| Applied gross pressure | 185 kPa |
| Allowable | 359.8 kPa |
|---|---|
| Ultimate | 1,079.4 kPa |
| Overburden | 21.6 kPa |
| Eff. width | 2.1 m |
| Allowable minus applied | 174.8 kPa |
| Wedge effective unit weight γeff | 10.19 kN/m³ |
| Cohesion factor Nc | 34.242 |
| Overburden factor Nq | 19.981 |
| Unit-weight factor Nγ | 17.7 |
| Cohesion contribution | 534.2 kPa |
| Overburden contribution | 431.6 kPa |
| Soil wedge contribution | 113.7 kPa |
| Width after eccentricity B′ | 2.1 m |
| Length after eccentricity L′ | 2.1 m |
| Cohesion / surcharge inclination factor | 1 |
| Wedge inclination factor | 1 |
| Effective plan area | 3.46 m² |
| Gross allowable load | 1,246.2 kN |
Engineering screening estimates. Use site-specific boring logs, appropriate test data and review by a licensed geotechnical PE before design or construction.
Engineering screening estimates. Use site-specific boring logs, appropriate test data and review by a licensed geotechnical PE before design or construction.
Worked result
Moist weight governs the overburden. The bearing wedge is submerged, and the circular shape factor applies to its contribution.
- The governing effective dimension is 2.1 m. Overburden q′ is 21.6 kPa and the wedge unit weight is 10.193 kN/m³.
- Add cohesion, overburden and wedge contributions of 534.183 kPa, 431.588 kPa and 113.666 kPa to get qᵤ = 1,079.437 kPa.
- Divide qᵤ by 3 to get a gross allowable pressure of 359.812 kPa.
Allowable359.8 kPaUltimate1,079.4 kPaOverburden21.6 kPaEff. width2.1 m
Original case inputs
| Bearing method | Terzaghi |
|---|---|
| Footing shape | Circle |
| Width or diameter B | 2.1 m |
| Base depth Df | 1.2 m |
| Cohesion c′ | 12 kPa |
| Friction angle φ′ | 29 ° |
| Moist weight γ | 18 kN/m³ |
| Saturated weight γsat | 20 kN/m³ |
| Water table depth Dw | 1.2 m |
| Bearing safety factor | 3 |
| Applied gross pressure | 185 kPa |
Method & assumptions
- qᵤ = c′·Nc·sc·dc·ic + q′·Nq·sq·dq·iq + ½ γeff·B′·Nγ·sγ·dγ·iγ. The conservative gross allowable screen is qᵤ / F.S. Compare against vertical service load per effective area.
- Effective overburden q′ sums moist soil above the water table and buoyant soil below it. The wedge term averages moist and buoyant unit weights over the smaller effective dimension below the base.
- Terzaghi uses his general shear Nq and Nc factors and linearly interpolates tabulated Nγ. Strip, square and circular shape factors follow the general shear model. For a rectangle, use the ratio of the smaller to the larger effective dimension.
- Meyerhof uses Nq = exp(π tan φ′) tan²(45° + φ′/2), Nc = (Nq − 1) cot φ′ and Nγ = (Nq − 1) tan(1.4φ′). Depth factors use the original width in Df/B. The circular screen uses a unit plan aspect ratio for vertical load.
- Plan eccentricity reduces B′ = B − 2eₓ and L′ = L − 2eᵧ. Inclined Meyerhof loading uses a centered load, unit shape factors and angle θ from vertical. The wedge factor reaches zero at θ ≥ φ′ for frictional soil. Check sliding, settlement and contact separately.
More worked examples
- Dry strip footing in sandA continuous wall bears on medium-dense sand. The seasonal water table lies below the bearing wedge.
- Square footing with water at gradeA square column pad supports a service load in saturated sand during the high-water season.
- Water table within a footing wedgeThe water table is 1.2 m below the base of a 2.4 m wide rectangular footing.
- Eccentric rectangular footing by MeyerhofA column moment shifts the vertical service load toward one edge of a rectangular pad.
- Undrained strip footing in clayAn idealized short-term total-stress check treats 42 kPa as undrained cohesion with φ = 0.
- Embedded square footing by MeyerhofAn embedded square pad bears in a dense granular layer below loose surface fill.