GlassFacadeLab · Solar absorption · Edge restraint
Partially shaded corner lite
Worked example · SI
Pass · Modeled edge tension is within the entered allowance.
Inputs
- Solar absorptance
- 0.57
- Peak solar irradiance
- 1050 W/m²
- Indoor reference temperature
- 26 °C
- Shaded edge temperature
- 17 °C
- Frame shadow band
- 110 mm
- Effective heat transfer
- 15 W/(m²·K)
- Edge finish
- Clean-cut
- Glass treatment
- Fully tempered
- Clean-cut annealed allowance
- 16 MPa
Results
- Center–edge ΔT
- 48.9 K
- Edge stress
- 29.82 MPa
- Edge allowance
- 48 MPa
- Safety factor
- 1.61
- Sunlit center temperature
- 65.9 °C
- Shaded edge temperature
- 17 °C
- Absorbed solar flux
- 598.5 W/m²
- Frame restraint assumption
- 0.968
- Edge stress utilization
- 62.1 %
Formula trace in SI
Absorbed heat
qsolar = α I; Tcenter = Tindoor + qsolar/heff
Absorbed 598.5 W/m², center 65.9 °C.
Edge tension
σth = E αglass max(ΔT, 0) Kframe
ΔT 48.9 K, Kframe 0.968, stress 29.822 MPa.
Edge allowance
σallow = σref × edge factor × treatment factor
Factors 1 × 3, allowance 48 MPa.