Adjustable instantaneous pickup
An adjustable breaker is modeled with a required 7.5 × pickup and a lower available voltage factor.
Device threshold met. Compared with the pickup for the selected protective device.
- Fault loop impedance
- 0.395 Ω
- Earth-fault current
- 535.7 A
- Maximum permissible Zₛ
- 0.44783 Ω
- CPC area at modeled current
- 1.4985 mm²
Inputs
| Earthing arrangement | TN-S |
|---|---|
| Nominal line-to-earth U₀ | 230 V |
| Minimum voltage factor | 0.92 × |
| External impedance Zₑ | 0.09 Ω |
| Phase resistance R₁ | 0.12 Ω |
| CPC resistance R₂ | 0.13 Ω |
| Resistance temperature factor | 1.22 × |
| Protective device | Custom magnetic multiplier |
| Breaker rated current In | 63 A |
| Guaranteed trip multiple | 7.5 × |
| Clearing / design time | 0.16 s |
| Protective conductor k | 143 A√s/mm² |
Derived values
| Protective device threshold | 472.5 A |
|---|---|
| Zₛ headroom | 0.052831 Ω |
| Fault current above threshold | 63.196 A |
| Warm phase / CPC resistance | 0.1464 Ω / 0.1586 Ω |
| Next size for modeled fault duty | 1.5 mm² |
| Supply voltage after cₘᵢₙ | 211.6 V |
Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.