GroundGridLab · IEC 60364 · NEC 250 context
TN-C-S C20 workshop branch
A workshop supply splits the upstream PEN at the intake. The downstream branch has a separate CPC and a C20 device.
Device threshold met. Compared with the pickup for the selected protective device.
- Fault loop impedance
- 0.82 Ω
- Earth-fault current
- 266.46 A
- Maximum permissible Zₛ
- 1.0925 Ω
- CPC area at modeled current
- 1.1785 mm²
Inputs
| Earthing arrangement | TN-C-S |
|---|---|
| Nominal line-to-earth U₀ | 230 V |
| Minimum voltage factor | 0.95 × |
| External impedance Zₑ | 0.22 Ω |
| Phase resistance R₁ | 0.22 Ω |
| CPC resistance R₂ | 0.26 Ω |
| Resistance temperature factor | 1.25 × |
| Protective device | C curve · 10 × In |
| Breaker rated current In | 20 A |
| Clearing / design time | 0.4 s |
| Protective conductor k | 143 A√s/mm² |
Derived values
| Protective device threshold | 200 A |
|---|---|
| Zₛ headroom | 0.2725 Ω |
| Fault current above threshold | 66.463 A |
| Warm phase / CPC resistance | 0.275 Ω / 0.325 Ω |
| Next size for modeled fault duty | 1.5 mm² |
| Supply voltage after cₘᵢₙ | 218.5 V |
Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.