Worked example · IEC 60364 · NEC 250 context

Type D motor feeder

TN-S and TN-C-S loop impedance, protection threshold and adiabatic CPC area.

A motor branch uses a high magnetic pickup to tolerate inrush. The higher trip multiple reduces the maximum acceptable loop impedance.

Device threshold shortfall

Compared with the pickup for the selected protective device.

Fault loop impedance
0.674 Ω
Earth-fault current
324.18 A
Maximum permissible Zₛ
0.34141 Ω
CPC area at modeled current
1.0138 mm²

Inputs

Circuit return path
V
×
Ω
Ω
Ω
×
Protection and CPC
A
s
A√s/mm²
Use the value for the material, insulation and starting temperature.

Phase-to-PE fault loop

Live schematic
Loop Zs0.674 ΩFault current324.2 AZs limit0.3414 ΩCPC area1.014 mm²TN-S · METALLIC LOOPR₁ phase 0.216 ΩR₂ protective 0.288 ΩEarthed sourceFaulted loadZₑ 0.17 ΩPROTECTIVE DEVICE CHECKProspective earth-fault current324.2 ADevice threshold640 ALoop impedance headroom-0.3326 ΩLoop impedance / limit197.4%
The fault returns on PE and, in TN-C-S, through the upstream PEN. The parallel earth paths are omitted.

Derived values & comparisons
Protective device threshold640 A
Zₛ headroom-0.33259 Ω
Fault current above threshold-315.82 A
Warm phase / CPC resistance0.216 Ω / 0.288 Ω
Next size for modeled fault duty1.5 mm²
Supply voltage after cₘᵢₙ218.5 V

Screening scope. Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.

Try this. Compare Type D and a manufacturer-specified custom multiple for the same measured loop components.

Calculation method

IEC 60364-4-41 and IEC 60364-5-54. Zₛ = Zₑ + (R₁ + R₂) × temperature factor, with the floor current Iₑꜰ = U₀cₘᵢₙ/Zₛ and limit Zₛ,ₘₐₓ = U₀cₘᵢₙ/Iₐ. Resistances are added as a scalar screening approximation.

The B, C and D defaults use 5, 10 and 20 times In, respectively. For a gG fuse, enter the total-clearing current read from the manufacturer’s curve at the entered time. Use the manufacturer’s curve to determine disconnection time.

The adiabatic calculation is S = Iₑꜰ√t/k for the entered duty. Check the maximum relevant I²t and the applicable mechanical minimum separately. NEC Article 250 describes the effective ground-fault current path and has its own conductor sizing requirements.

Standards and model assumptions