GroundGridLab · IEC 60364 · NEC 250 context
gG fuse with specified curve point
The fuse manufacturer’s total-clearing curve is assumed to give a 190 A threshold at the entered time. The number is an illustrative curve input.
Device threshold met. Compared with the curve current for the selected protective device.
- Fault loop impedance
- 0.896 Ω
- Earth-fault current
- 243.86 A
- Maximum permissible Zₛ
- 1.15 Ω
- CPC area at modeled current
- 1.3411 mm²
Inputs
| Earthing arrangement | TN-S |
|---|---|
| Nominal line-to-earth U₀ | 230 V |
| Minimum voltage factor | 0.95 × |
| External impedance Zₑ | 0.26 Ω |
| Phase resistance R₁ | 0.24 Ω |
| CPC resistance R₂ | 0.29 Ω |
| Resistance temperature factor | 1.2 × |
| Protective device | gG fuse · curve current |
| Current from fuse curve | 190 A |
| Clearing / design time | 0.4 s |
| Protective conductor k | 115 A√s/mm² |
Derived values
| Protective device threshold | 190 A |
|---|---|
| Zₛ headroom | 0.254 Ω |
| Fault current above threshold | 53.862 A |
| Warm phase / CPC resistance | 0.288 Ω / 0.348 Ω |
| Next size for modeled fault duty | 1.5 mm² |
| Supply voltage after cₘᵢₙ | 218.5 V |
Verify actual loop impedance, the manufacturer’s clearing curve and device breaking capacity. Size the CPC for worst-case let-through I²t and the applicable minimum area. NEC 250 uses separate bonding and equipment grounding provisions.